NUT-SCANNER(8)
==============

NAME
----

nut-scanner - scan communication buses for NUT devices

SYNOPSIS
--------

*nut-scanner* -h

*nut-scanner* ['OPTIONS']

DESCRIPTION
-----------

*nut-scanner* scans available communication buses and displays any
NUT-compatible devices it has found.

*nut-scanner* can also display the detected devices in various formats,
including ups.conf, and ensures that the generated devices name are unique
across buses.

INSTALLATION
------------

*nut-scanner* is only built if libltdl (part of libtool development suite)
is available. Available options (USB, SNMP, IPMI, ...) will vary according
to the available compile time and runtime dependencies. For example, if
Net-SNMP is installed, thus providing libsnmp (.so or .dll) and headers,
both during compilation and runtime, then SNMP discovery will be available.

OPTIONS
-------

*-h*::
Display the help text.

DISPLAY OPTIONS
---------------

*-Q* | *--disp_nut_conf_with_sanity_check*::
Display result in the 'ups.conf' format with sanity-check warnings (if any)
as comments (default).

*-N* | *--disp_nut_conf*::
Display result in the 'ups.conf' format.

*-P* | *--disp_parsable*::
Display result in a parsable format.

BUS OPTIONS
-----------

*-C* | *--complete_scan*::
Scan all available communication buses (default behavior)

*-U* | *--usb_scan*::
List all NUT-compatible USB devices currently plugged in.
+
This option can be specified several times, for more hardware link-specific
details; these can be counter-productive in case of USB enumeration changes
over time:
+
| `-U`    | do not report any bus/device/busport details |
| `-UU`   | report bus and busport, if available |
| `-UUU`  | report bus/device/busport details |
| `-UUUU` | report bus/device/busport details, and bcdDevice (limited use and benefit) |
+
NOTE: For reliability, it is preferable to match just by vendor and product
identification, and a serial number if available and unique.

*-S* | *--snmp_scan*::
Scan SNMP devices. Requires at least a 'start IP', and optionally,
an 'end IP'. See specific SNMP OPTIONS for community and security settings.

*-M* | *--xml_scan*::
Scan XML/HTTP devices. Can broadcast a network message on the current network
interfaces to retrieve XML/HTTP capable devices. No IP required in this mode.

*-O* | *--oldnut_scan*::
Scan NUT devices (i.e. upsd daemon) on IP ranging from 'start IP' to 'end IP'.

*-n* | *--nut_simulation_scan*::
Scan NUT simulated devices (.dev files in $CONFPATH).

*-A* | *--avahi_scan*::
Scan NUT servers using Avahi request on the current network interfaces.
No IP required.

*-I* | *--ipmi_scan*::
Scan NUT compatible power supplies available via IPMI on the current host,
or over the network.

*-E* | *--eaton_serial* 'serial ports'::
Scan Eaton devices (XCP and SHUT) available via serial bus on the current host.
This option must be requested explicitly, even for a complete scan.
'serial ports' can be expressed in various forms:

- 'auto' to scan all serial ports.
- a single character indicating a port number ('0' (zero) for /dev/ttyS0 and
/dev/ttyUSB0 on Linux, '1' for COM1 on Windows, 'a' for /dev/ttya on Solaris...)
- a range of N characters, hyphen separated, describing the range of
ports using 'X-Y', where X and Y are characters referring to the port number.
- a single port name.
- a list of ports name, coma separated, like '/dev/ttyS1,/dev/ttyS4'.

NETWORK OPTIONS
---------------

*-t* | *--timeout* 'timeout'::
Set the network timeout in seconds. Default timeout is 5 seconds.

*-s* | *--start_ip* 'start IP'::
Set the first IP (IPv4 or IPv6) when a range of IP is required (SNMP, old_nut)
or optional (XML/HTTP).

*-e* | *--end_ip* 'end IP'::
Set the last IP (IPv4 or IPv6) when a range of IP is required (SNMP, old_nut)
or optional (XML/HTTP).
If this parameter is omitted, only the 'start IP' is scanned. If 'end IP' is
less than 'start IP', both parameters are internally permuted.

*-m* | *--mask_cidr* 'IP address/mask'::
Set a range of IP using CIDR notation.

NUT DEVICE OPTION
-----------------

*-p* | *--port* 'port number'::
Set the port number of scanned NUT devices (default 3493).

SNMP V1 OPTION
--------------

*-c* | *--community* 'community'::
Set SNMP v1 community name (default = public).

SNMP V3 OPTIONS
---------------

*-l* | *--secLevel* 'security level'::
Set the 'security level' used for SNMPv3 messages.
Allowed values are: noAuthNoPriv, authNoPriv and authPriv.
This parameter is mandatory if you use non-trivial authentication.

*-u* | *--secName* 'security name'::
Set the 'security name' used for authenticated SNMPv3 messages.
This parameter is mandatory if you set 'security level'.

*-w* | *--authProtocol* 'authentication protocol'::
Set the 'authentication protocol' used for authenticated SNMPv3 messages.
Allowed values are MD5, SHA, SHA256, SHA384 or SHA512 (depending on
Net-SNMP library capabilities; check help of the `nut-scanner` binary
program for the run-time supported list). Default value is MD5.

*-W* | *--authPassword* 'authentication pass phrase'::
Set the 'authentication pass phrase' used for authenticated SNMPv3 messages.
This parameter is mandatory if you set 'security level' to authNoPriv
or authPriv.

*-x* | *--privProtocol* 'privacy protocol'::
Set the 'privacy protocol' used for encrypted SNMPv3 messages.
Allowed values are DES, AES, AES192 or AES256 (depending on Net-SNMP
library capabilities; check help of the `nut-scanner` binary program
for the run-time supported list). Default value is DES.

*-X* | *--privPassword* 'privacy pass phrase'::
Set the 'privacy pass phrase' used for encrypted SNMPv3 messages.
This parameter is mandatory if you set 'security level' to authPriv.

IPMI OPTIONS
------------

*-b* | *--username* 'username'::
Set the username used for authenticating IPMI over LAN connections
(mandatory for IPMI over LAN. No default).

*-B* | *--password* 'password'::
Specify the password to use when authenticating with the remote host
(mandatory for IPMI over LAN. No default).

*-d* | *--authType* 'authentication type'::
Specify the IPMI 1.5 authentication type to use (NONE, STRAIGHT_PASSWORD_KEY,
MD2, and MD5) with the remote host (default=MD5).
This forces connection through the 'lan' IPMI interface , thus in IPMI 1.5 mode.

*-L* | *--cipher_suite_id* 'cipher suite identifier'::
Specify the IPMI 2.0 cipher suite ID to use. The Cipher Suite ID identifies
a set of authentication, integrity, and confidentiality algorithms to use
for IPMI 2.0 communication.
+
The authentication algorithm identifies the algorithm to use for session
setup, the integrity algorithm identifies the algorithm to use for session
packet signatures, and the confidentiality algorithm identifies the algorithm
to use for payload encryption (default=3).
+
The following cipher suite ids are currently supported
(Authentication; Integrity; Confidentiality):

- *0*: None; None; None
- *1*: HMAC-SHA1; None; None
- *2*: HMAC-SHA1; HMAC-SHA1-96; None
- *3*: HMAC-SHA1; HMAC-SHA1-96; AES-CBC-128
- *6*: HMAC-MD5; None; None
- *7*: HMAC-MD5; HMAC-MD5-128; None
- *8*: HMAC-MD5; HMAC-MD5-128; AES-CBC-128
- *11*: HMAC-MD5; MD5-128; None
- *12*: HMAC-MD5; MD5-128; AES-CBC-128
- *15*: HMAC-SHA256; None; None
- *16*: HMAC-SHA256; HMAC_SHA256_128; None
- *17*: HMAC-SHA256; HMAC_SHA256_128; AES-CBC-128

MISCELLANEOUS OPTIONS
---------------------

*-V* | *--version*::
Display NUT version.

*-a* | *--available*::
Display available buses that can be scanned, depending on how the nut-scanner
binary program has been compiled. (e.g. OLDNUT, USB, SNMP, XML, AVAHI, IPMI).

*-q* | *--quiet*::
Display only scan result. No information on currently scanned bus is displayed.

*-D* | *--nut_debug_level*::
Raise the debugging level.  Use this multiple times to see more details.

NOTE: The level of debugging needed depends both on nut-scanner and the
problem you're trying to diagnose.  Therefore, first explain the problem you
have with `nut-scanner` to a developer/maintainer, before sending them debugging
output.  More often than not, if you just pick a level, the output may be
either too limited or too verbose to be of any use.

EXAMPLES
--------

To scan USB devices only:

----
:; nut-scanner -U

[nutdev-usb1]
        driver = "snmp-ups"
        port = "192.168.0.42"
----

To scan SNMP v1 device with public community on address range 192.168.0.0
to 192.168.0.255:

----
:; nut-scanner -S -s 192.168.0.0 -e 192.168.0.255

[nutdev-snmp1]
        driver = "snmp-ups"
        port = "192.168.0.42"
----

The same using CIDR notation:

----
:; nut-scanner -S -m 192.168.0.0/24

[nutdev-snmp1]
        driver = "snmp-ups"
        port = "192.168.0.42"
----

To scan NUT servers with a timeout of 10 seconds on IP range 192.168.0.0
to 192.168.0.127 using CIDR notation:

----
:; nut-scanner -O -t 10 -m 192.168.0.0/25

[nutdev-nut1]
        driver = "dummy-ups"
        port = "dummy-test@192.168.1.28"
----

To scan for power supplies, through IPMI (1.5 mode) over the network,
on address range 192.168.0.0 to 192.168.0.255 using CIDR notation:

----
:; nut-scanner -I -m 192.168.0.0/24 -b username -B password
----

To scan for Eaton serial devices on ports 0 and 1 (`/dev/ttyS0`,
`/dev/ttyUSB0`, `/dev/ttyS1` and `/dev/ttyUSB1` on Linux):

----
:; nut-scanner --eaton_serial 0-1
----

To scan for Eaton serial devices on ports 1 and 2 (`COM1` and `COM2` on Windows):

----
:; nut-scanner --eaton_serial 1-2
----

SEE ALSO
--------

linkman:ups.conf[5]

Internet resources:
~~~~~~~~~~~~~~~~~~~

The NUT (Network UPS Tools) home page: https://www.networkupstools.org/